Quote Not Generating Correctly

Last updated: Feb 2026   

Estimated time to complete: 5 min.   

Applies to: Air Conditioning Engineers

Summary

Step-by-step diagnostic guide for when quotes show incorrect pricing, missing equipment, or unexpected results.


If a quote isn't generating as expected - wrong total, missing equipment, or no equipment selected at all, work through the checks below in order. Each step targets the most common causes, starting with the simplest fixes.

Step-by-Step Guide

Step 1. Check Your Equipment Catalogue


The quote builder selects equipment from your Equipment Catalogue. If the catalogue is empty or incomplete, the system can't generate a valid selection.


  • Do you have indoor units added? Go to Equipment Catalogue and check the Indoor Units tab
  • Do you have outdoor units added? Check the Outdoor Units tab
  • Are the units marked as active? Inactive units are excluded from selection
  • Do the units have trade prices set? Units with a £0 trade price may produce incorrect totals

Important

If your Equipment Catalogue is empty, the quote builder cannot select any equipment. Add at least one indoor unit, one outdoor unit, and one compatibility rule before creating quotes.

Step 2. Check Compatibility Rules


The system needs to know which indoor units work with which outdoor units. Without compatibility rules, it can't build a valid system.


Go to Equipment Catalogue > Compatibility tab

Check that each indoor unit is linked to at least one outdoor unit

Verify the maximum connected capacity percentage is set correctly (typically 100–130%)

If you've recently added new units, make sure you've also added their compatibility entries

Warning

A common mistake is adding new equipment models but forgetting to set up their compatibility rules. The quote builder will skip any units that have no compatible pairings.

Step 3. Verify Room configuration


The cooling capacity required for each room is calculated from the room dimensions and type. Incorrect values here will produce incorrect equipment selections.


Check room dimensions are in metres (not centimetres or feet)

Verify the room type matches the actual space, different room types have different watts-per-square-metre calculations

Make sure at least one room has been added to the quote

Check that room dimensions are realistic — a 0.5m × 0.5m room will calculate very low cooling requirements

Note

The watts-per-square-metre rate used for calculations is configured in your Settings. If all your quotes seem consistently over- or under-sized, check this value.

Step 4. Review Pricing Settings


If the equipment selection looks correct but the total price is wrong, the issue is likely in your pricing configuration.


  • Labour rate - check your day rate or hourly rate is set correctly in Settings
  • Equipment margin - if you've set a margin percentage, it's applied on top of trade prices
  • Installation margin - a separate margin applied to labour costs
  • Materials costs - check fixed materials, per-unit materials, brackets, consumables, and pipework rates
  • Additional costs - electrician fees, parking charges, and contingency percentages all add to the total
  • VAT rate - verify this matches your current VAT obligation


Step 5. Check Brand Preferences


If you've selected a brand preference on the quote, the system will only choose equipment from that brand. This can cause issues if:


The selected brand has no compatible units for the required capacity

The brand's units are all marked as inactive

The brand has indoor units but no outdoor units (or vice versa)



Note

Try removing the brand preference and resubmitting the quote. If equipment is now selected, the issue is with the specific brand's catalogue entries.

Step 6. Check Capability Tolerance Settings


Your settings include tolerance and connected capacity percentages that control how closely the selected equipment must match the calculated requirement. If these are set too tightly, the system may not find a valid combination.


Tolerance percentage - how much over or under the calculated capacity is acceptable (e.g. 10% means a 5kW requirement accepts 4.5–5.5kW units)


Connected capacity range - the minimum and maximum percentage of the outdoor unit's capacity that can be used by connected indoor units


Warning

Setting the tolerance too low (e.g. 0%) means only an exact capacity match is accepted, which may result in no valid equipment selection. A tolerance of 10–20% is recommended.

Still Not Working?

If you've checked all the above and the quote still isn't generating correctly:


  • Try creating a simple test quote with one room and no brand preference to isolate the issue
  • Check the Quick Fix Guide for other common problems
  • Contact support with the quote number and a description of what you expected vs what you got — we can investigate from our end

Did this answer your question?

Great! We’re glad we could help.

Save Time. Close More Deals. Grow Profit.


Get Quotestack updates delivered directly to your inbox.

Contact Us